Página 1 - Fieldbus I/O

Rev.6 EM07ZS1647FEPSON RC+ Option Fieldbus I/O

Página 2

Table of Contents 2.9 DeviceNet Board Installation ... 54 2.9.1 Board Appearance ...

Página 3

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Disconnected terminating resistors { Cable dis

Página 4 - WARRANTY

4. Troubleshooting (DeviceNet) 4.1.2.3 Master: Unestablished Communication Master Unit LED MS NS Error Description Green Light ON Light OFF Master Un

Página 5

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Voltage drop of communications power supply Me

Página 6 - SUPPLIERS

4. Troubleshooting (DeviceNet) 4.1.2.4 Master: Configuration Error Master Unit LED MS NS Error Description Red Light Blinking No Matter Configuratio

Página 7 - Before Reading This Manual

4. Troubleshooting (DeviceNet) ♦ Process Flowchart 7 Check Finish The unit is not found.Immediately The unit is found. Yes  No Change No change The

Página 8

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Master unit configuration (1) Start applicomIO

Página 9

4. Troubleshooting (DeviceNet) 4.1.2.5 Absent Slave Master Unit LED MS NS Error Description Light OFF Green Light Blinking Absent slave - No slave (E

Página 10

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Voltage drop of communications power supply Me

Página 11 - Fieldbus I/O Rev.6 ix

4. Troubleshooting (DeviceNet) 4.1.2.6 Uninitialized Network Master Unit LED MS NS Error Description Light OFF Light OFF Uninitialized network Abse

Página 12

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Voltage drop of communications power supply Me

Página 13 - 1. Introduction

Table of Contents 5. Maintenance Parts List ... 151 Appendix A applicomIO Upgrade...

Página 14 - 1.2 DeviceNet

4. Troubleshooting (DeviceNet) 4.1.3 Procedures for Examining Possible Causes 4.1.3.1 Connection Problem (Disconnected Terminating Resistors, Cable D

Página 15

4. Troubleshooting (DeviceNet) ♦ Process Flowchart Check that terminating resistors are connected. Measure resistance with tester. 50 to 70 Ω Norma

Página 16 - General Specifications

4. Troubleshooting (DeviceNet) 4.1.3.2 Loose Connector and Signal Wire Check for the connections of the following parts on the connector and cable.

Página 17 - 1.3 PROFIBUS DP

4. Troubleshooting (DeviceNet) 4.1.3.3 Noise Intrusion Verify how an error occurrence condition changes while taking the following countermeasures. ♦

Página 18

4. Troubleshooting (DeviceNet) Countermeasure 2: Disconnect the shield wire to isolate it from the ground. When noise intrudes the ground line becaus

Página 19

4. Troubleshooting (DeviceNet) ♦ Communications Power Supply When sharing one power source with the communications power supply and I/O devices, prov

Página 20 - 1.4 EtherNet/IP

4. Troubleshooting (DeviceNet) 4.1.3.4 Broken Unit Examination (Dividing Network Examination) When you cannot quickly find the trouble point due to a

Página 21

4. Troubleshooting (DeviceNet) (2) Separate each slave from the network Check for each slave. The trouble point is where error condition changes i

Página 22

4. Troubleshooting (DeviceNet) 4.1.3.6 EPSON RC+ Master Configuration For details of EPSON RC+ master configuration, refer to the section 2.5 DeviceN

Página 23 - 2. Installation

4. Troubleshooting (DeviceNet) 4.1.3.6.2 Verifying the DeviceNet network condition The applicomIO Console application has a network diagnostic functi

Página 24

Table of Contents x Fieldbus I/O Rev.6

Página 25

4. Troubleshooting (DeviceNet) (2) Select the DeviceNet (Scanner) tab. The window changes as shown below. MAC ID : MAC ID specified for the scan

Página 26

4. Troubleshooting (DeviceNet) Status Code General ProtocolDescriptions 45 Non-resident dialogue software. Additional information: Initialize the

Página 27

4. Troubleshooting (DeviceNet) (3) When you click the I/O button on the upper left of the window, the window changes as shown below. Each slave dev

Página 28

4. Troubleshooting (PROFIBUS DP) 4.2 PROFIBUS DP Troubleshooting Exclusion Every system has its special environment, conditions, specifications, and

Página 29 - Shield Wire

4. Troubleshooting (PROFIBUS DP) 4.2.1 Examining a Problem 4.2.1.1 Scanner Board Diagnostic LEDs The PROFIBUS DP board used with EPSON RC+ has two st

Página 30 - 0.6 mm 3.5 mm

4. Troubleshooting (PROFIBUS DP) 4.2.1.2 Check Network Status First of all, you should check the current condition of the network. There are differ

Página 31

4. Troubleshooting (PROFIBUS DP) 4.2.2 Problems and Countermeasures Master Unit LED BF ST Error Description [Reference] Light OFF Green Light Blinki

Página 32

4. Troubleshooting (PROFIBUS DP) ♦ Process Flowchart Master: Physical Error Slave: Communication ErrorYesYesYes1Master: Communication ErrorYesMaster

Página 33

4. Troubleshooting (PROFIBUS DP) 4.2.2.1 Master: Communication Error Master Unit LED BF ST Error Description Light OFF Red Light Blinking Communicati

Página 34

4. Troubleshooting (PROFIBUS DP) ♦ Process Flowchart Replace the unit. 1 No Problem Check Check the following: - Unconnected terminating resistor -

Página 35 - 40 mm 7.5 mm

1. Introduction 1. Introduction 1.1 Overview of Fieldbus I/O The Fieldbus I/O option is an integrated I/O system that supports DeviceNet, PROFIBUS DP

Página 36

4. Troubleshooting (PROFIBUS DP) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Disconnected terminating resistors { Cable d

Página 37

4. Troubleshooting (PROFIBUS DP) 4.2.2.1.2 Slave: Data Link Error MS NS Master LED Condition Light OFF Red Light BlinkingAbsent Slave LED Conditi

Página 38 - 2.7.1 Board Appearance

4. Troubleshooting (PROFIBUS DP) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Disconnected terminating resistors { Cable di

Página 39 - 2.7.3 Software Installation

4. Troubleshooting (PROFIBUS DP) 4.2.2.1.3 Slave: Uninitialized Network BF ST Master LED Condition Light OFF Red Light BlinkingAbsent Slave LED Con

Página 40

4. Troubleshooting (PROFIBUS DP) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Electrical surges of device power supply Meas

Página 41 - 2.7.4 Board Installation

4. Troubleshooting (PROFIBUS DP) 4.2.2.1.4 Slave: Physical Error BF ST Master LED Condition Light OFF Red Light BlinkingAbsent Slave LED Condition

Página 42

4. Troubleshooting (PROFIBUS DP) 4.2.2.2 Master: Data Link Layer Error Master Unit LED BF ST Error Description Light OFF Red Light ON Data link layer

Página 43 - 2.7.5 Master Mode

4. Troubleshooting (PROFIBUS DP) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Disconnected terminating resistors{ Cable dis

Página 44

4. Troubleshooting (PROFIBUS DP) 4.2.2.3 Master: Uninitialized Network Master Unit LED BF ST Error Description Light OFF Light OFF Uninitialized netw

Página 45

4. Troubleshooting (PROFIBUS DP) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Electrical surges of master device power supp

Página 46

1. Introduction 1.2 DeviceNet Overview of DeviceNet DeviceNet is a fieldbus network that provides easy interconnection between control devices (PLC,

Página 47

4. Troubleshooting (PROFIBUS DP) 4.2.2.4 Master: Configuration Error Master Unit LED BF ST Error Description Red Light ON No Matter Physical error -

Página 48

4. Troubleshooting (PROFIBUS DP) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Disconnected terminating resistors { Cable di

Página 49 - 2.7.6 Slave Mode

4. Troubleshooting (PROFIBUS DP) 4.2.3 Procedures for Examining Possible Causes 4.2.3.1 Connection Problem (Disconnected Terminating Resistors, Cable

Página 50

4. Troubleshooting (PROFIBUS DP) ♦ Process Flowchart Normal See 4.2.3.2. Turn OFF all units. Normal Resistance: over 120 ΩMeasure resistance at con

Página 51

4. Troubleshooting (PROFIBUS DP) 4.2.3.2 Loose Connector and Signal Wire Check for the connections of the following parts on the connector and cable.

Página 52

4. Troubleshooting (PROFIBUS DP) Countermeasure 1: Improve FG. Peel the cable covering and secure the cable with FG clamps.Grounding ScrewIsoelect

Página 53 - 2.8.1 Board Appearance

4. Troubleshooting (PROFIBUS DP) 4.2.3.4 Broken Unit Examination (Dividing Network Examination) When you cannot quickly find the trouble point due to

Página 54 - 2.8.3 Software Installation

4. Troubleshooting (PROFIBUS DP) 4.2.3.5 Network Configuration and Specifications (1) Maximum Cable Length Check that the cables used on the network

Página 55

4. Troubleshooting (PROFIBUS DP) 4.2.3.6 EPSON RC+ Master Configuration For details of EPSON RC+ master configuration, refer to the section 2.6 PROFI

Página 56 - 2.8.4 Board Installation

4. Troubleshooting (PROFIBUS DP) 4.2.3.6.2 Verifying the PROFIBUS DP network condition The applicomIO Console application has the following function

Página 57

1. Introduction Different Connection Types There are two messaging connections: I/O messaging connection and explicit messaging connection. The I/O

Página 58 - 2.8.5 Master Mode

4. Troubleshooting (PROFIBUS DP) (3) Select the Protocol | Diagnostic on the applicomIO Console application menu. Click the magnifying grass button

Página 59

4. Troubleshooting (PROFIBUS DP) (4) When you click the I/O button, the window changes as shown below. The status of each slave device is shown in

Página 60

4. Troubleshooting (EtherNet/IP) 4.3 EtherNet/IP Troubleshooting Exclusion Every system has its special environment, conditions, specifications, and

Página 61

4. Troubleshooting (EtherNet/IP) 4.3.1 Examining a Problem 4.3.1.1 Scanner Board Diagnostic LEDs The EtherNet/IP board used with EPSON RC+ has two s

Página 62

4. Troubleshooting (EtherNet/IP) 4.3.1.2 Check Network Status (1) Master Status: MS/NS LEDs LED Color Light Condition MS (Module Status)  Green 

Página 63 - 2.8.6 Slave Mode

4. Troubleshooting (EtherNet/IP) 4.3.2 Problems and Countermeasures Master Unit LED MS NS Error Description [Reference] Green Light ON Green Light ON

Página 64

4. Troubleshooting (EtherNet/IP) 4.3.3 Tests and diagnostics 4.3.3.1 The diagnostic tool After configuring the EtherNet/IP master, adding and configu

Página 65 - 2.8.7 GSD File

4. Troubleshooting (EtherNet/IP) 1. Diagnostic of the TCP/IP layer This screen is used to display the exchange statuses regarding the TCP/IP layer.

Página 66 - 2.9.2 Specifications

4. Troubleshooting (EtherNet/IP) TCP tab Passive connections Number of passive connections. Active connections Number of active connections. Curren

Página 67 - 2.9.3 Software Installation

4. Troubleshooting (EtherNet/IP) 2. Diagnostic of server devices Requests Number of requests. Requests / s umber of requests per second. Useful byt

Página 68

1. Introduction General Specifications Electrical Specifications Item Specification Supply Voltage 5 V DC (supplied from a controller) Power Consump

Página 69 - 2.9.4 Board Installation

4. Troubleshooting (EtherNet/IP) 3. Overall device diagnostics View the diagnostic information on a device in the configuration by selecting the node

Página 70

4. Troubleshooting (EtherNet/IP) 4.3.3.1.2 TCP/IP tool By clicking in the button and selecting "TCP/IP layer", a "services" win

Página 71

4. Troubleshooting (EtherNet/IP) 2. Ping ICMP ECHO "PING" functionality is available on the applicomIO solution. It is available through

Página 72 - 2.9.5 Master Mode

5. Maintenance Parts List 5. Maintenance Parts List Part Name Code Specifications DeviceNet board R13B040701 PROFIBUS DP board R13B040702 Eth

Página 73

5. Maintenance Parts List 152 Fieldbus I/O Rev.6

Página 74

Appendix A applicomIO Upgrade Appendix A applicomIO Upgrade (1) Start the controller (2) Insert the setup CD that is packaged with the product to

Página 75

Appendix A applicomIO Upgrade (7) Following dialog appears. Select the option above. (If the option below is selected, the transition of the curre

Página 76 - 2.9.6 Slave Mode

Appendix A applicomIO Upgrade (10) Select the protocol and the device data file. (11) Complete the installation. (12) The message to ensure the

Página 77 - Fieldbus I/O Rev.6 65

Appendix A applicomIO Upgrade 156 Fieldbus I/O Rev.6

Página 78

1. Introduction 1.3 PROFIBUS DP Overview of PROFIBUS DP PROFIBUS DP is one of fieldbus networks that provide easy interconnection between control dev

Página 79

1. Introduction Functions of Master There are two types of PROFIBUS DP master: DPM1 and DPM2. DPM1 (DP Master Class 1) gathers and controls all stat

Página 80 - 68 Fieldbus I/O Rev.6

1. Introduction General Specifications Electrical Specifications Item Specification Supply Voltage 5 V DC (supplied from a controller) Power Consump

Página 81 - 3. Operation

E PSON RC+ Option Fieldbus I/O Rev.6

Página 82

1. Introduction 1.4 EtherNet/IP Overview of EtherNet/IP EtherNet/IP is a fieldbus network that provides easy interconnection between control devices

Página 83 - 3.5 Using FbusIO_SendMsg

1. Introduction Large Numbers of Inputs/Outputs For EPSON RC+ standard I/O and expansion I/O, the number of inputs/outputs is limited to 512 inputs a

Página 84 - 3.7 Remote Control Slave

1. Introduction General Specifications Electrical Specifications Item Specification Supply Voltage 5 V DC (supplied from a controller) Power Consump

Página 85 - SEIKO EPSON

2. Installation 2. Installation This chapter contains procedures for installing a DeviceNet, PROFIBUS DP, or EtherNet/IP network. Refer to the secti

Página 86 - DeviceNet

2. Installation 2.2 DeviceNet Network Construction Network Configuration A DeviceNet network is configured as shown in the following figure. Commun

Página 87 - PROFIBUS DP

2. Installation Thick Cable Thin Cable Braid Shield Signal Wire (Blue/White)Power Wire (Red/Black) 11.2 to 12.1 mm outside diameter Shield W

Página 88 - 76 Fieldbus I/O Rev.6

2. Installation Maximum Network Length (Maximum Trunk Length) The maximum network length is the longest distance either between terminating resistors

Página 89 - 4. Troubleshooting

2. Installation Total Drop Line Length The total drop line length is the total distance of all drop lines on one network. Trunk Line2 m2 m1 m 1 m 3

Página 90 - 4.1.1 Examining a Problem

2. Installation If the current capacity consumed on the network exceeds the restriction of cable current capacity, it is possible to install more tha

Página 91

2. Installation (2) Carefully expand the meshes of the braided shield. Under the braided shield, there is one exposed bare twisted shield wire other

Página 92

EPSON RC+ Option Fieldbus I/O Rev.6 Copyright © 2005-2007 SEIKO EPSON CORPORATION. All rights res

Página 93 - Fieldbus I/O Rev.6 81

2. Installation (7) Tighten each screw securing the wires on the connector. Tighten the screw securing the wire at a correct tightening torque (0.2

Página 94 - No Problem

2. Installation 2.3 How to Setup a PROFIBUS DP Network The following is a basic procedure for setting up a PROFIBUS DP network: 1. Choose station di

Página 95

2. Installation 2.4 PROFIBUS DP Network Construction Network Configuration A PROFIBUS DP network is configured as shown in the following figure. Sla

Página 96 - 84 Fieldbus I/O Rev.6

2. Installation It is recommended that a 9-pin D-Sub connector be used for protecting rating IP 20. For IP 65/67, M12 connector in accordance with I

Página 97

2. Installation PROFIBUS DP requires approximately 1ms at 12 Mbps for the transmission of 512 bits input data and 512 bits output data distributed ov

Página 98

2. Installation Procedure for Modifying and Installing Communication Cables The following procedure explains how to modify and install a Woodhead 9-p

Página 99 - Fieldbus I/O Rev.6 87

2. Installation 2.5 How to Setup a EtherNet/IP Network The following is a basic procedure for setting up a EtherNet/IP network: 1. Choose node distr

Página 100

2. Installation 2.6 EtherNet/IP Network Construction Network Configuration A EtherNet/IP network is configured as shown in the following figure. Net

Página 101

2. Installation 2.7 DeviceNet Board Installation Following two types can be used for the fieldbus I/O option DeviceNet. - PCU-DVNIO - PCI-DVNIO 2.7.1

Página 102

2. Installation 2.7.2 Specifications Part Number applicom PCI-DVNIO / PCU-DVNIO Modes Master/Slave Baud rates 125, 250, 500 kbps Interface 1 Devic

Página 103

FOREWORD This manual contains important information necessary to use the EPSON RC+ option Fieldbus I/O properly and safely. This manual is intended

Página 104 - 92 Fieldbus I/O Rev.6

2. Installation (6) Allow the default components to be installed. (7) Select the protocol: DeviceNet you will be using. If you also use PROFIBUS

Página 105

2. Installation 2.7.4 Board Installation WARNING  Make sure that the power is turned OFF before installing/removing any boards or connecting/disco

Página 106

2. Installation is shown in the Board Type: box. Then, click the OK button. When installing more than two fieldbus boards in the system, add all the

Página 107

2. Installation 2.7.5 Master Mode (1) Ensure that the board is connected to the fieldbus. Then, start the applicomIO console application. (2) Regi

Página 108

2. Installation (6) Configure the baud rate, MAC ID (master address), and so on for the DeviceNet network. The load on a bus can be controlled by

Página 109

2. Installation (9) Drag each device you want to scan from the Network Detection tab to the Master item in the list on the right. (10) The followin

Página 110 - Blue (CAN L)Red (CAN H)

2. Installation The Expert Mode button will appear when the applicomIO Console application is used in the expert mode. To configure details of “Chan

Página 111

2. Installation To create a new EDS file based on the data from the device, click the Create New EDS File button. When a new EDS file is created, th

Página 112

2. Installation (13) Select File | Download in Flash to register the configuration in the fieldbus board. After a few seconds, the board's st

Página 113 - ♦ Ground of FG (DRAIN) wire

2. Installation 2.7.6 Slave Mode (1) Ensure that the board is connected to the fieldbus. Then, start the applicomIO console application. (2) Click

Página 114 - Light electrical cable

TRADEMARKS Microsoft, Windows, and Windows logo are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or o

Página 115 - Power Supply Tap

2. Installation (6) The DeviceNet Local Slave property sheet will appear. Select the Equipment (device) ID. It must be the same number as the Mast

Página 116

2. Installation (9) Select File | Download in Flash to register the configuration in the fieldbus board. After a few seconds, the board's stat

Página 117 - Ω 1/4 W

2. Installation $ EDS File Generated by applicomIO® Console Version : 2.2 [File] DescText = "EDS for applicomIO Scanner"; CreateDa

Página 118

2. Installation 2.8 PROFIBUS DP Board Installation Following two board types can be used for the fieldbus I/O option PROFIBUS DP. - PCU-DPIO - PCI-D

Página 119

2. Installation 2.8.2 Specifications Part Number applicom PCI-DPIO / PCU-DPIO Modes Master/Slave Baud Rates 9.6, 19.2, 93.75, 187.5, 500, 1500, 30

Página 120

2. Installation (6) Allow the default components to be installed. (7) Select the protocol: PROFIBUS DP you will be using. If you also use Devic

Página 121

2. Installation 2.8.4 Board Installation WARNING  Make sure that the power is turned OFF before installing/removing any boards or connecting/disco

Página 122

2. Installation (8) The following dialog will appear. Check that “PCI-DPIO” or “PCU-DPIO” (“PCI-DVNIO” in case of DeviceNet) is shown in the Board

Página 123 - Exclusion

2. Installation 2.8.5 Master Mode (1) Ensure that the board is connected to the fieldbus. Then, start the applicomIO console application. (2) Regi

Página 124 - 4.2.1 Examining a Problem

2. Installation (5) Select the “Profibus, Master/Slave” in the Channel Properties dialog and click the OK button. (6) Click on the “Protocol list

Página 125

MANUFACTURER & SUPPLIER Japan & Others SEIKO EPSON CORPORATION Suwa Minami Plant Factory Automation Systems Dept. 1010 Fujimi, Fuji

Página 126

2. Installation (9) Click the Network Detection tab on the center left of the console window. (10) Click the Read Network Configuration button to

Página 127

2. Installation (12) The following dialog will appear. The device name is shown on the dialog title bar. Click the OK button. When the system cannot

Página 128

2. Installation (13) Select the Equipment Library tab on the center left of the console window and click the Add button to register the new GSD fil

Página 129

2. Installation 2.8.6 Slave Mode (1) Ensure that the board is connected to the fieldbus. Then, start the applicomIO console application. (2) Select

Página 130 - ♦ Causes of Error

2. Installation (6) Configure the baud rate, Master Profibus Address (slave address), number of repeaters, and so on for the PROFIBUS DP network. I

Página 131

2. Installation (9) Select File | Download in Flash to register the configuration in the fieldbus board. After a few seconds, the board's stat

Página 132

2. Installation 2.9 EtherNet/IP Board Installation Following two board types can be used for the fieldbus I/O option EtherNet/IP. - PCU-ETHIO 2.9.1

Página 133

2. Installation 2.9.3 Software Installation Before installing any boards in your controller, you must install the applicomIO console application and

Página 134

2. Installation (7) Select the protocol: Ethernet you will be using. If you also use DeviceNet, select DeviceNet as well. If you also use PROFIBU

Página 135

2. Installation 2.9.4 Board Installation WARNING  Make sure that the power is turned OFF before installing/removing any boards or connecting/disco

Página 136

Before Reading This Manual This section describes what you should know before reading this manual. Safety Precautions Installation and transportatio

Página 137

2. Installation (8) The following dialog will appear. Check that “PCI/PCU-ETHIO (“PCI-DVNIO” in case of DeviceNet, and ”“PCI-DPIO” or “PCU-DPIO” in

Página 138

2. Installation (10) Click the OK button. The following dialog will appear. Configure the IP address for the EtherNet/IP board. Select the IP addre

Página 139

2. Installation 2.9.5 Master Mode (1) Ensure that the board is connected to the fieldbus. Then, start the applicomIO console application. (2) Regi

Página 140

2. Installation (3)-3 Check the device information in EDS, and click the Next button. (3)-4 Click the Complete button to register the EDS file. (

Página 141

2. Installation (6) Drag each device you want to scan from the Network Detection tab to the Master item in the list on the right. (7) Following d

Página 142

2. Installation After a few seconds, the board's state will show green in the status bar. Now, the fieldbus board is ready to operate as a mast

Página 143

2. Installation 2.9.6 Slave Mode (1) Ensure that the board is connected to the fieldbus. Then, start the applicomIO console application. (2) Doubl

Página 144 - ♦ Ground of FG wire

2. Installation (6) Drag EtherNet/IP Local Slave from Equipment Library to the Master item in the list on the right. Window in step 5 appears. Con

Página 145

2. Installation (9) The default slave EDS file is created. The path is: C:\Program Files\Woodhead\Direct-link\ApplicomIO2.3\ConfigIO \Config01\appl

Página 146

2. Installation 2.10 EPSON RC+ Fieldbus I/O Installation After you have created your fieldbus network and installed the scanner board(s) in your cont

Página 147

vi Fieldbus I/O Rev.6

Página 148

2. Installation 68 Fieldbus I/O Rev.6

Página 149

3. Operation 3. Operation This chapter contains information on how to use the Fieldbus I/O option after it has been installed. 3.1 Fieldbus I/O Addre

Página 150

3. Operation 3.3 Outputs Off by Emergency Stop and Reset Instruction You can configure the system so that all outputs including the fieldbus outputs

Página 151

3. Operation 3.5 Using FbusIO_SendMsg FbusIO_SendMsg is used to send an explicit message to a device and return a reply. This command operates accor

Página 152

3. Operation 3.6 Using Slave Mode In slave mode, the EPSON RC+ system is a slave on the bus. Outputs from the master are inputs in EPSON RC+, and in

Página 153 - 4.3.1 Examining a Problem

3. Operation 3.8 Devices available for Fieldbus I/O Option The fieldbus I/O option operations were checked with the following devices. )NOTE The fol

Página 154

3. Operation 3.9 Fieldbus I/O Response Performance As mentioned previously, respond times for fieldbus I/O can vary and depend on several factors. Th

Página 155

3. Operation PROFIBUS DP Test Environment RC520 Controller: Pentium III 850 MHz 128 MB memory Fieldbus I/O: PCI-DPIO board Master (station address:

Página 156 - 4.3.3 Tests and diagnostics

3. Operation 76 Fieldbus I/O Rev.6

Página 157

4. Troubleshooting (DeviceNet) 4. Troubleshooting 4.1 DeviceNet Troubleshooting Exclusion Every system has its special environment, conditions, speci

Página 158

Table of Contents 1. Introduction ... 1 1.1 Overview of Fieldbus I/O...

Página 159

4. Troubleshooting (DeviceNet) 4.1.1 Examining a Problem 4.1.1.1 Scanner Board Diagnostic LEDs The DeviceNet board used with EPSON RC+ has two statu

Página 160

4. Troubleshooting (DeviceNet) 4.1.1.2 Check Network Status (1) Master Status: MS/NS LEDs LED Color Light Condition MS (Module Status)  Green  R

Página 161

4. Troubleshooting (DeviceNet) 4.1.2 Problems and Countermeasures Master Unit LED MS NS Error Description [Reference] Green Light ON Green Light ON N

Página 162

4. Troubleshooting (DeviceNet) ♦ Process Flowchart Master: Absent Slave Master Unit: Configuration Error Master: Unestablished Communication Master

Página 163 - 5. Maintenance Parts List

4. Troubleshooting (DeviceNet) 4.1.2.1 Master: Communication Error Master Unit LED MS NS Error Description Green Light ONRed Light Blinking Communica

Página 164 - 152 Fieldbus I/O Rev.6

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Slave power OFF Measure the power voltage of

Página 165

4. Troubleshooting (DeviceNet) ♦ Process Flowchart Replace the unit. 2  No Problem Check Check the following: - Unconnected terminating resistor -

Página 166

4. Troubleshooting (DeviceNet) ♦ Causes of Error Possible Cause Examination Method Countermeasure { Disconnected terminating resistors{ Cable disc

Página 167

4. Troubleshooting (DeviceNet) 4.1.2.2 Master: Busoff Detection Master Unit LED MS NS Error Description Busoff detection Communication stopped due t

Página 168 - 156 Fieldbus I/O Rev.6

4. Troubleshooting (DeviceNet) ♦ Process Flowchart Replace the unit. 5 No Problem Check Check the following: - Unconnected terminating resistor - U